Turbo-Lux 3 is a MECON fire pump test meter / flowmeter for sprinkler systems. The TL3B0-LR variant appears in the official MECON Turbo-Lux 3 datasheet as an order code for the 8"/DN 200 configuration.
Technical Specification
Bypass flow meter for Turbo-Lux 3 set (spare part)
workings
Measurement principle: bypass meter (floating body)
Installation position: vertical
Measurement accuracy
Measurement deviation: ±2.0% of the end value of the measurement range (FM)
± 5.0% of measurement value (LPCB)
±2.5% of the final measurement range value (vDS)
process conditions
Nominal size: 8"/DN 200 (ø 219.1 mm)
Pump rated power: 2500 usGpm
Display range: 1000 — 5000 usGPM
3800 - 19000 lpm
operating conditions
Medium: water
Operating temperature: +4 to +50 °C
max. operating pressure: FM 500 psi (34.5 bar)
LPCB/ VdS PN 16 (232 psi)
Constructive structure
Differential pressure collection tube: brass
Floater: stainless steel
Side flow valve: stainless steel
Filter screen: stainless steel
Seal: NBR
Certificates/Approvals FM
LPCB
VdS